Fisher DLC3010 Digital Level Controller

The FIELDVUE DLC3010 digital level controller is used with level sensors to measure liquid level, the level of the interface between two liquids, or liquid specific gravity (density). Changes in level or specific gravity exert a buoyant force on a displacer, which rotates a torque tube shaft. The digital level controller converts

this rotational motion to an electronic signal.



DLC3010 Digital Level Controller Specifications

Available Configurations

DLC3010 Digital Level Controller:

Mounts on caged and cageless 249 sensors. See

tables 4 and 5 and sensor description.

Function: Transmitter

Communications Protocol: HART

Input Signal

Level, Interface, or Density: Rotary motion of torque

tube shaft proportional to changes in liquid level,

interface level, or density that change the buoyancy

of a displacer.

Process Temperature: Interface for 2- or 3-wire

100 ohm platinum RTD for sensing process

temperature, or optional user-entered target

temperature to permit compensating for changes in

specific gravity


Output Signal

Analog: 4 to 20 milliamperes DC ( direct

action—increasing level, interface, or density

increases output; or  reverse action—increasing

level, interface, or density decreases output)

High saturation: 20.5 mA

Low saturation: 3.8 mA

High alarm: 22.5 mA

Low Alarm: 3.7 mA

Only one of the above high/low alarm definitions is

available in a given configuration. NAMUR NE 43

compliant when high alarm level is selected.

Digital: HART 1200 Baud FSK (frequency shift keyed)

HART impedance requirements must be met to

enable communication. Total shunt impedance

across the master device connections (excluding the

master and transmitter impedance) must be between

230 and 600 ohms. The transmitter HART receive

impedance is defined as:

Rx: 42K ohms and

Cx: 14 nF

In point-to-point configuration, analog and digital

signalling are available. The instrument may be

queried digitally for information, or placed in Burst

mode to regularly transmit unsolicited process

information digitally. In multi-drop mode, the output

current is fixed at 4 mA, and only digital

communication is available.